Economical online conductivity controller, 1 to 3 points calibration, 4 to 20mA signal output. The meter is suitable for monitoring the conductivity and TDS of the water quality.
Features:
• Economical online conductivity controller contains TDS measurement mode.
• 1 to 3 points calibration with automatic calibration solution recognition.
• Selectable cell constant, temperature coefficient and TDS conversion factor.
• Automatic Temperature Compensation ensures accurate reading.
• Low and high alarm limits can be set by user and automatically activate an external device.
• 4 to 20mA output signal meets industry standard.
• Manual temperature calibration improves the measurement accuracy of meter.
• Selectable temperature unit (°C or °F) for different application requirements.
• System menu allows setting the 9 parameters, including the number of calibration points,
cell constant, alarm limits, hysteresis value, etc.
• Reset feature automatically resumes all settings back to factory default settings.
Model |
BI-650 |
|
Conductivity |
||
Range |
0~20.00, 200.0, 2000µS/cm, 20.00, 200.0mS/cm |
|
Accuracy |
±1% F.S |
|
Resolution |
0.01, 0.1, 1 |
|
Calibration Points |
1 to 3 points |
|
Calibration Solutions |
84uS/cm, 1413uS/cm, 12.88mS/cm, 111.8mS/cm |
|
TDS |
||
Range |
0~100ppt (Max. 200ppt, depending on factor setting) |
|
Accuracy |
±1% F.S |
|
TDS Factor |
0.1~1.0 (Default 0.5) |
|
Temperature |
||
Range |
0~100°C, 32~212°F |
|
Accuracy |
±1°C |
|
Resolution |
0.1°C |
|
Communication |
||
Signal Output |
4~20mA |
|
Load |
Max. 500Ω |
|
Low and high alarm limits |
0.02uS/cm~20.0mS/cm, Selectable |
|
Communication Interface |
RS485 |
|
Connection Terminals |
Detachable screw terminals |
|
Others |
||
Temperature Compensation |
0~100°C, 32~212°F, Automatic |
|
Temperature Coefficient |
0.0~10.0%/°C |
|
Cell Constant |
K=0.1, 1, 10 |
|
Normalization Temperature |
25°C |
|
Environmental Conditions |
0~60°C, 32~140°F |
|
Power Requirements |
DC24V |
|
Dimensions |
96(L)×96(W)×75(H)mm |
|
Weight |
350g |